Probable Causes | Solutions |
---|---|
Power Supply not connected to switchboard | Connect Power Supply to the Incomer Breaker |
Control MCBs for Indication Ckt. are off or Control Fuses are blown off | Switch "ON" the MCBs or replace Control Fuse Links whichever is applicable |
Indicating Lamps are faulty | Replace Indicating Lamps |
No Control Supply Available | Check for rated Control Supply to the switchboard at the terminals provided as per wiring drawing. |
Probable Causes | Solutions |
---|---|
Closing on Short Circuit | Remove the fault after detection and than close the Circuit Breaker after inspection of circuit breaker condition |
ACB is not completely in Service Position | Check whether ACB spring is charged* |
Check whether U/V Release is picked up | |
Check for any Mechanical or Electrical Interlocking | |
Check whether Trip command is issued by any Feeder Protection Relay/Device & resolve. | |
Reset Button Signalling a Fault Trip has not been reset | Remove the fault after detection and than close the Circuit Breaker after inspection of circuit breaker condition |
No Control Supply Available* | Connect rated Control Supply to the switchboard at the terminals provided as per wiring drawing. |
Control MCB is "Off"* | Switch "ON" the Control MCBs |
Selection for Local Mode is not done* | Select Local Mode |
Closing command not executed by Closing Coil | Check the voltage and the supply circuit, if problem persists replace the Closing Coil |
Interlocking Ckt. Not working | Check for proper control voltage/Micro PLC UPS Supply. If problem persists contact STANDARD CONTROL PANEL PVT. LTD. Mobile: +91-98764-00718, +91-99884-20003 |
Plug-in terminals provided at Transport Section not connected | Connect the Plug-in terminals |
Breaker Control Switch Faulty | Replace faulty Breaker Control Switch. |
Probable Causes | Solutions |
---|---|
Opening command not executed byTripping Coil | Check the voltage and the supply circuit, if problem persists replace the Tripping Coil |
Welded contacts of the Circuit Brekers | Contact STANDARD CONTROL PANEL PVT. LTD. Mobile: +91-98764-00718, +91-99884-20003 |
No Control Supply Available | Check for rated Control Supply to the switchboard at the terminals provided as per wiring drawing. |
Breaker Control Switch Faulty | Replace faulty Breaker Control Switch. |
Probable Causes | Solutions |
---|---|
Circuit Breaker in Closed/On condition | Open the Circuit Breaker |
Probable Causes | Solutions |
---|---|
Presence of any Rack In/Out Interocking | Follow correct Interlocking sequence |
Probable Causes | Solutions |
---|---|
U/V Release supply too low | Check the voltage and the supply circuit, if problem persists replace the U/V Release |
Wrong operation sequence done manually | Follow the correct operation sequence and restore supply |
Tripping on Fault (i.e. Overload, Shortcircuit, Earthfault) | Remove the fault after detection and than close the Circuit Breaker after inspection of circuit breaker condition |
Probable Causes | Solutions |
---|---|
Feeder SCPD i.e.(MCCB, SDFU, MCB) is in 'OFF' condition | Switch'ON' the Feeder SCPD |
Thermal O/L relay is in Trip Conditon | Reset the O/L relay by means of reset push button on the relay |
Start push button is not working properly | Check start push button element for proper working |
Local Mode selection not done | Select Local Mode through selector switch provided on Feeder Door |
Any interlocking is preventing the Starter Operation | Check for proper operating seqence. |
Probable Causes | Solutions |
---|---|
Primarly Check for any probable cause as covered under Starter Operation Locally. | Resolve the problem as suggested above |
Remote mode selection not done | Select Remote Mode through selector switch provided on Feeder Door |
Any wiring fault for remote close command | Check for Fault and resolve. |
Probable Causes | Solutions |
---|---|
No Control Supply Available | Connect rated Control Supply to the switchboard at the terminals provided as per wiring drawing. |
Control MCB is "Off" | Switch "ON" the Control MCBs |
Probable Causes | Solutions |
---|---|
No Power Supply Available | Connect Power Supply to the Feeder |
Control MCBs for PT Ckt. are off or Control Fuses are blown off | Switch "ON" the MCBs or replace Control Fuse Links whichever is applicable |
Probable Causes | Solutions |
---|---|
CT shorting terminals provided in Metering Feeder are still short | Open the shorting link by loosening and sliding down the shorting link |
No load on the Feeder | Can be checked after putting some load on the feeder. |
Probable Causes | Solutions |
---|---|
SCPD (i.e. MCCBs, SDFU) for the Capacitor Bank Feeder is in 'OFF' condition | Switch 'ON' the SCPD for capacitor bank feeder |
C.T.shorting link is not open at Trf. End. | Open the C.T. shorting link |
Auto' selection not done for Capacitor Bank Feeders | Select 'Auto' mode for Feeders by selector switch provided on the feeder door |
APFC Relay not in 'Auto' mode. | Put the relay in 'Auto' mode. Refer the Relay User Manual |
Sensing current to the relay is too low. | Opt for a suitable rating Fixed Capacitor Bank. Consult STANDARD CONTROL PANEL PVT. LTD. Mobile: +91-98764-00718, +91-99884-20003 |
Capacitor Bank are faulty and rejected by APFC Relay | Replace Capacitor Bank. Consult STANDARD CONTROL PANEL PVT. LTD. Mobile: +91-98764-00718, +91-99884-20003 |
Pre programmed parameters disturbed at site | Check for current programmed parameters and correct if required or cont. STANDARD CONTROL PANEL PVT. LTD. Mobile: +91-98764-00718, +91-99884-20003 |
Probable Causes | Solutions |
---|---|
DG is not started after Set Time Delay | Check for Released Emergency Push Button, key in 'ON' condition. |
No Control Supply Available | Check for rated Control Supply to the switchboard at the terminals provided as per wiring drawing. |
Start Command Not Executed by DG Set | Contact respective DG Service Centre |
D.G. set is not in Remote mode | Put the D.G. in Remote mode by D.G. controller or cont to D.G. vendor |
AMF Relay not in 'Auto' mode. | Put the relay in 'Auto' mode. Refer the Relay User Manual |
Fault Signalled by relay | Attend and resolve the fault. If the problem persist call STANDARD CONTROL PANEL PVT. LTD. Mobile: +91-98764-00718, +91-99884-20003 |